Test Flashcards Preview

311 AFFF > Test > Flashcards

Flashcards in Test Deck (26)
Loading flashcards...
1

What type of AFFF stations do we have onboard?

Type 3 balance pressure proportioner system

2

What is the capacity of each AFFF tank?

300 gallons

3

Which spaces are protected by AFFF sprinkling station #1?

Engine room
Fire room

4

Which AFFF hose reels are serviced by AFFF station #1?

E/R L/L Port & STBD
E/R U/L Port & STBD
F/R L/L Port & STBD
F/R U/L Port
E/R Re-entry
F/R Re-entry

5

Which spaces are protected by AFFF sprinkling from station #2?

Flight deck
SSDG

6

Which AFFF hose reels are serviced by AFFF station #2?

Flight deck Port & STBD
SSDG Port & STBD
SSDG Re-entry

7

What valve controls the flow of Firemain to the AFFF station?

The Hycheck valve

8

What valve controls the flow of AFFF concentration from the tank?

Powercheck valve

9

Name the types of power sources each AFFF station has.

Normal
Alternate
Casualty

10

Which sound powered phone circuit do AFFF operators use?

X50J

11

How many gallons of AFFF concentrate are located at the AFFF refill stations?

165 gallons or 3-55 gallon drums

12

What piece of equipment is used when replenishing the AFFF tank?

Hand pump

13

True or False: BLUERIDGE has an installed AFFF concentrate transfer system.

FALSE

14

Besides the cross connect valve located in each station, where is the 3rd valve that has to be opened prior to cross-connecting the 2 stations?

EM P-way outside mooring station 7

15

What is the allowable operating pressure of firemain in the AFFF system?

80 psi

16

What does SOPV stand for?

Solinoid operating pilot valve

17

How many SOPV valves are located in each station?

3 each

18

How many "master SOPV" valves are in each station?

1 each

19

What is the function of master SOPV?

Directs water away from hycheck and directs to powercheck so both valves open

20

What is the purpose of the balancing valve?

Maintains a balance pressure of AFFF concentrate to firemain in order to maintain 94% to 6% ratio

21

What is the purpose of the proportioner?

Mixes AFFF concentrate with firemain to make solution

22

What toxic gas is normally found associated in AFFF systems?

H2S or hydrogen sulfide

23

Where are the location of the flight deck sprinkling activation buttons?

FWD part of Miser tower
HCO tower

24

Where are the location of the enginerooom bilge sprinkling activation buttons?

Main control
Near escape ellision door
Port side 4th deck entrance
STBD side 4th deck entrance

25

Where are the location of the fire room bilge sprinkling activation buttons?

Near BTOW console
Near escape ellision door
4th deck STBD side entrance

26

Where are the location of the SSDG bilge sprinkling activation buttons?

Near ladder to SSDG
Inside EOS
4th deck access