PEC CHAPTER 8 COMMUNICATION SYSTEMS Flashcards Preview

PEC > PEC CHAPTER 8 COMMUNICATION SYSTEMS > Flashcards

Flashcards in PEC CHAPTER 8 COMMUNICATION SYSTEMS Deck (8)
Loading flashcards...
1
Q

COMMUNICATION CIRCUITS

Wires and Cables Outside of the Building (Clearance):

On Poles and In-Span - Supply service drops of _______V running above and parallel to communications service drops shall have a minimum separation of________(mm) at any point in the span, including the point of and at their attachment to the building.

A

0-750 volts

300 mm

2
Q

COMMUNICATION CIRCUITS

Wires and Cables Outside of the Building (Clearance):

Above Roofs - Shall have a vertical clearance of not less than______(mm) from all points of the roof which they pass.

A

2500 mm

3
Q

COMMUNICATION CIRCUITS

Wires and Cables Outside of the Building (Clearance):

Lighting Conductors - A separation of at least ______(mm) shall be between communications wires and cables on buildings and lightning conductors

A

1800 mm

4
Q

RADIO AND TELEVISION EQUIPMENT

Clearances - Receiving Stations

Outside of Buildings - Lead-in conductors attached to buildings shall be installed so that they cannot swing closer than ______(mm) to the conductors of circuits of ______V or less between conductors, or _____(mm) to the conductors of circuits of over _____V between conductors, except that in the case of circuits not over ___V between conductors, where all conductors involved are supported so as to ensure permanent separation, the clearance shall be permitted to be reduced but shall not be less than ____(mm).

A

600 mm

250V

3000 mm

250V

150V

100 mm

5
Q

RADIO AND TELEVISION EQUIPMENT

Clearances - Receiving Stations

From Lighting Rod Systems - The clearance shall not be less than______(mm)

A

1800 mm

6
Q

RADIO AND TELEVISION EQUIPMENT

Clearances - Receiving Stations

Underground Conductors - Shall be separated at least _____(mm) from conductors of any light or power circuits or Class 1 circuits.

A

300 mm

7
Q

RADIO AND TELEVISION EQUIPMENT

Clearances - Receiving Stations

Antennas and Lead-ins (Indoors) - Shall not be run nearer than ___(mm) to conductors of other wiring systems in the premises.

A

50 mm

8
Q

.

A

.